MSKC-HA High voltage switch characteristic comprehensive tester
MSKC-HA High voltage switch characteristic comprehensive tester
Product Description
Magus MSKC-HA high voltage switch characteristic comprehensive tester measures opening/closing time, bounce time, speed, stroke and coil current for SF6, GIS, vacuum and oil circuit breakers. 12 channels, 9-inch touch screen, built-in DC6~270V power supply. Ideal for substations and power engineering contractors.
The Magus MSKC-HA High Voltage Switch Characteristic Comprehensive Tester is a 12-channel circuit breaker analyzer designed for substations, power engineering contractors, and HV test engineers . It accurately measures opening/closing time, bounce time, speed, stroke, and coil current for SF6, GIS, vacuum, and oil circuit breakers.
Built to GB1984-2014 and DL/T846.3-2017, the MSKC-HA delivers laboratory-grade accuracy in a rugged, field-ready package — with a 9-inch touch screen, built-in DC6~270V power supply, and one-operation data capture.
Why Choose the Magus MSKC-HA?
– **One operation, all data** — Capture time, speed, stroke, bounce and graphics in a single switch action
– **12 fracture channels** — 6 main + 6 auxiliary contacts measured simultaneously
– **Built-in DC power supply** — DC6~270V adjustable, 20A, no external secondary power needed
– **9-inch color touch screen** — Windows OS, Chinese & English input, intuitive for field use
– **Multi-sensor support** — Linear, rotation, universal and laser sensors (optional)
– **Wide compatibility** — SF6, GIS, vacuum and oil circuit breakers
– **Anti-interference design** — Reliable operation in 500KV substations
– **Large storage** — 30,000 test records, expandable, with real-time clock
– **USB + RS232 + WIFI** — Easy data export and optional remote operation
—
Key Applications
– Substation commissioning and maintenance
– Circuit breaker mechanical characteristic testing
– SF6 and GIS switchgear diagnostics
– Vacuum circuit breaker testing
– Oil circuit breaker testing
– Low voltage operation tests
– Reclosing tests (C-O, O-C, O-C-O)
– Aging tests
– Vibration frequency analysis
—
Technical Specifications
| Test Item | Technical Specifications |
| Time Measurement | • 12 channels for inherent opening / closing time • Supports different periods in opening/closing phase, phase difference, bounce time & bounce times • Different period test range: 0.01ms~99ms, resolution: 0.01ms • Internal trigger: 1ms~999ms (0.01ms); 1000ms~9999ms (0.1ms); 10000ms~200000ms (1ms) • External trigger: 0.01ms~200s • Accuracy (≤1000ms): 0.05% ±0.1ms |
| Speed Measurement | • Just-opening / just-closing speed • Average speed over specified stroke / angle period • Linear sensor: 0.01 ~ 20.00 m/s, accuracy: 0.05% ±0.1ms • 345° angle sensor: 0.01 ~ 20.00 m/s, accuracy: 0.05% ±0.1ms • Laser sensor: 0.01 ~ 15.00 m/s |
| Stroke Measurement | • Moving contact stroke (3‑way stroke measurement optional) • Contact stroke (open distance), overtravel, overshoot / rebound stroke • Linear sensor: 0‑50mm, resolution: 0.1mm • 345° rotation sensor: 0‑1000mm, resolution: 0.08° ⚠️ Note: 15° invalid zone; recommended effective display angle: 160–200° • Acceleration sensor: 0‑300mm, resolution: 0.1mm • Accuracy: ±(1%L+0.2)mm |
| Coil Current Test | • Max current: 20A, resolution: 0.01A • Accuracy: ±5% |
| Coil Resistance Test | • Range: 0~2000Ω, resolution: 0.01Ω • Accuracy: ±5% |
| Instrument Power Supply | • AC220V ±10%; 50Hz ±10% |
| DC Power Output | • DC6 ~ 270V continuously adjustable • DC24V ≤15A (short‑time); DC220V ≤20A (short‑time) |
| External Trigger | • AC/DC 10–300V, current ≤120A |
| Isolating Switch Measurement | • Output voltage: DC6~270V adjustable • Output time: 0.01–20s (configurable) •Max fracture‑signal collection time: 200s • Testable items: fracture opening/closing time, three‑phase asynchronism, bounce time & bounce frequency |
| Dimension & Environment | • Host size: 450 × 400 × 220 mm• Operating temperature: -20℃ ~ +50℃• Relative humidity: ≤90% |
Frequently Asked Questions (FAQ)
**Q1: What circuit breakers can the MSKC-HA test?**
A: SF6, GIS, vacuum and oil circuit breakers from all major manufacturers.
**Q2: Does it need an external power supply?**
A: No. The MSKC-HA has a built-in DC6~270V adjustable power supply, 20A.
**Q3: How many fractures can it measure at once?**
A: 12 fractures — 6 main and 6 auxiliary contacts.
**Q4: Can it measure speed without retesting?**
A: Yes. Speed can be recalculated from the same test data without re-operating the breaker.
**Q5: Is it suitable for 500KV substations?**
A: Yes. The internal anti-interference circuit is designed for reliable use in 500KV substations.
**Q6: What sensors are supported?**
A: Linear, rotation, universal and laser sensors (optional).
**Q7: How is data exported?**
A: Via 2 USB ports (U disk or mouse), RS232 (optional) and WIFI (optional).
**Q8: What is the warranty and support?**
A: Contact Magus for warranty details and technical support.