Secondary Injection Test Set for Power Relay Commissioning
MSJB-903 3 phase relay protection tester with 3×30A AC current & 4 phase voltage output. DSP+FPGA hardware, portable secondary injection test set for transformer differential, over current, distance protection field test
Product Overview
MSJB-903 3 phase relay protection tester is a portable secondary current injection test device for power system commissioning, maintenance and laboratory testing …. It delivers 3 phase current and 4 phase voltage output, supporting tests for conventional electromechanical relays as well as modern numerical micro processor protection relays. It performs outstandingly for transformer differential protection and standby automatic switching device testing, fully satisfying diverse on site test demands for power plants and substations Made-in-Ch….
This test set complies with GB/T 7261-2016 Basic testing method for relaying protection and security automatic equipment and DL/T 624-2010 Technical conditions for microcomputer based test device of relay protection Made-in-Ch…. Built in embedded industrial computer runs Windows XP system with one key system recovery function to prevent system crash caused by misoperation or illegal power off. It can work standalone or connect with laptop via USB port for remote control, sharing identical operation software without extra learning cost …
Key Features
Complete On site Test Capacity:3 phase current + 4 phase voltage output. Supports over current, distance, directional, impedance, harmonic, transformer differential, standby auto switching, fault recurrence and meter calibration tests. Ideal for substation & power plant relay commissioning.
Industrial Embedded Platform:10.4inch LED true color display (800×600 resolution). Equipped with shortcut keypad and optical touch pad, same operating experience as PC. System recovery function prevents crash from improper shutdown .
High Precision DSP+FPGA Hardware:16 bit DAC, generates 2000 sampling points per fundamental wave cycle for superior waveform quality and output accuracy. Frequency range 0-1000Hz, phase accuracy up to 0.1°.
High Fidelity Linear Power Amplifier: Excellent stability for both tiny and large current output. Built in hardware protection against over heat, over current, over voltage and short circuit. Hardware timing for high current output improves field safety.
Independent Auxiliary DC Power Supply :Built in DC auxiliary output: 110V/2A & 220V/1A, to supply working power for external protection relays.
Software Self Calibration: Calibrate accuracy by software instead of opening cabinet and adjusting potentiometer, ensures long term measuring stability.
Rich Digital I/O Terminals:8 pair digital input, 4 pair digital output. Recognizes both active and passive contact signals, maximum timing resolution 1 ms.
Portable & Compact:Weight only 12.5 kg, dimension 328 ×157 ×250 mm. USB 2.0 communication for data export, firmware upgrade and laptop connection. Grounding terminal and cooling fan ensure reliable field performanceMade-in-Ch….
Technical Specifications
AC Current Source (3×30A)
Item
Specifications
Singlephase AC Current(RMS)
030A / phase; Accuracy: 0.2% ±5mA
Threephase Parallel Output(RMS)
090A (inphase parallel)
Longterm allowable phase current
9.9A
Max power per phase
300 VA
Max power for 3phase parallel
800 VA
Max duration for 90A parallel output
5 s
Frequency Range
01000 Hz; Accuracy:0.01 Hz
Harmonic Output
220 orders
Phase Adjustment
0360°, Accuracy:0.1°
DC Current Source
Item
Specifications
DC Current Output
0±10 A / phase; Accuracy:0.5% ±5 mA
AC Voltage Source
Item
Specifications
Singlephase AC Voltage(RMS)
0120 V / phase; Accuracy:0.2% ±5 mV
Line Voltage Output(RMS)
0240 V
Output Power(Phase / Line)
75 VA /100 VA
Frequency
01000 Hz, Accuracy 0.01 Hz
Harmonic
220 orders
Phase
0360°, Accuracy 0.1°
DC Voltage Source
Item
Specifications
Singlephase DC Voltage
0±160 V; Accuracy:0.5% ±5 mV
DC Line Voltage
0320 V
Output Power(Phase / Line)
90 VA /180 VA
Digital Switching I/O
Item
Specifications
Digital Input
8 pairs; support active & passive contact, max DC 250V
Digital Output
4 pairs dry contact; Breaking capacity DC 030V/5A; AC 0250V/5A